Product Name | Switchgear Cabinets |
Item No. | XGN15-12 |
Supply Type | Sell |
Category | Electronic,Electrical > Electronic Component > Switch |
Technical Parameters:
SN | Name | Unit | Numerical value | Remark | |
1 | Rated voltage | kV | 12 | F,FR | |
2 | Rated frequency | Hz | 50 | F,FR | |
3 | Rated current | A | 630 | F,FR | |
4 | Maximum fuse current | A | 125 | F,FR | |
5 | Rated short time withstand current | kA | 25 | F | |
6 | Rated short circuit duration | S | 4 | F | |
7 | Rated peak withstand current | kA | 63 | F | |
8 | Rated short circuit making current | kA | 63 | F | |
9 | Rated active load breaking current | A | 630 | F | |
10 | Closed-loop breaking current | A | 630 | F | |
11 | Rated cable charging current | A | 10 | F | |
12 | Main loop resistance | μΩ | ≤150 | F | |
13 | Transfer current | A | 1700 | FR | |
14 | Rated short circuit breaking current | kA | 50 | FR | |
15 | Main loop resistance(excluding fuse) | μΩ | ≤250 | FR | |
16 | Same distance | mm | 210±5 | F,FR | |
17 | Maximum operating torque | Switching on | N.m | 8~100 | F,FR |
Switching of | N.m | ||||
18 | Maximum operating torque | Switching on | N.m | 8~100 | Earthing station |
Switching of | N.m | ||||
19 | Rated short time withstand current of earthing switch | kA | 25 | F | |
20 | Rated short circuit duration of earthing switch | S | 3 | F | |
21 | Rated peak withstand current of earthing switch | kA | 63 | F | |
22 | 1min rated short time power-frequency withstand voltage | Ph-ph, Ph-ground | kV | 42 | F,FR |
Breaker gap | 48 | ||||
23 | Rated lightning impulse withstand voltage | Ph-ph, Ph-ground | kV | 75 | |
Breaker gap | 85 | ||||
24 | Mechanical life | Load switch | Times | 2000 | |
Isolating switch | 2000 | ||||
25 | Protection class | IP3X |
Keywords: High Voltage Switchgear Switchgear switchgear cabinets