| GENSET MODEL |
AP-425 |
| Genset Manufacturer: ALL POWER |
| PRIME |
STANDBY |
| GENSET OUTPUT |
340KW |
374KW |
| GENSET OUTPUT |
425KVA |
467KVA |
| Rated speed / frequency |
1500 rpm / 50 Hz |
| SHORT CIRCUIT PROTECTION |
MCCB |
| VOLTAGE/FREQUENCY/POWER FACTOR |
400V/230V, 3 Phase and 4 Wires |
| Rated power factor |
0.8(lagging) |
| RELATIVE VOLTAGE ADJUST RANGE |
0~5% |
| MOMENT VOLTAGE ADJUST RATIO |
-15%~+20% |
| STEADY FREQUENCY ADJUST RATIO |
0~5% |
| MOMENT FREQUENCY ADJUST RATIO |
-7%~+10% |
| TIME OF STEADY VOLTAGE |
≤ 4s |
| TIME OF STEADY FREQUENCY |
≤ 3s |
| WINDAGE OF STEADY VOLTAGE |
≤ ±1% |
| FREQUENCY FLUCTUATION RATIO |
0.5% |
| Maximum output current(A) |
613 |
| DIESEL ENGINE MODEL |
NT12V135ZDHX |
| ENGINE MANUFACTURER |
Nantong Engine Company Ltd |
| Rated Output(KW) |
374 |
| ENGINE CONFIGURATION |
Water-cooled, 12 cylinders in V, 4-cycle, direct injection |
| ASPIRATION |
TURBOCHARGE |
| Bore(mm)×Stroke (mm) |
135X150 |
| Fuel consumption(g/kw.h) |
≤ 215 |
| Displacement (Liters) |
26.64 |
| Exhaust air flow(m3/min) |
440 |
| Compress air flow(m3/min) |
35 |
| Exhaust highest temperature |
510°C |
| Lub-oil pan capacity(L) |
57.4 |
| Cooling water capacity(L) |
61 |
| Voltage for start(V) |
24 |
| Instrument for adjusting speed |
MECHANICAL/ELECTRICAL |
| Noise level(A) |
≤ 96dBA(open) |
| ALTERNATOR |
| ALTERNATOR MODEL |
CHINESE ALTERNATOR |
| Excitation |
Brushless |
| Insulation class |
H |
| Protection class |
IP23 |
| Efficiency |
92.8% |
| Voltage adjust range |
≥ ±6% |
| Steady state voltage regulation |
≤ ±1% |
| Voltage Control |
AVR |
| Dimension(L*W*H) (mm) |
3300*1425*2060 |
| Weight(kg) |
3650 |